Four FR outlets on the output: devices plug straight in, with no adapter or special cord. 2200 W genuinely available for 2200 VA, a graphic LCD display and a slot for a network card.
4 FR outlets: devices plug straight in, with no adapter
2200 W genuinely available, power factor of 1
USB port and RS-232 serial port for automatic server shutdown
Slot for an SNMP, Modbus or dry contact network card
Pure sine wave output
Multilingual graphic LCD display
Shallow 3U format, tower-convertible
Accepted input voltage from 176 to 276 V
Terminal block for remote start-up and shutdown
Noise level below 40 dBA
Weight 24.5 kg
Ref.: 9PX2200IRTBPF
Out of stock
1/2
20 899,00 DHincl. VAT
Out of stock
Product overview
A high-end online UPS, convertible between rack and tower: online double conversion, 2200 VA / 2200 W, 3U format. Technology & protection: power is fully and continuously regenerated — your equipment is never exposed to the mains, with zero transfer time. Complete protection against outages, surges, voltage fluctuations and electrical noise. Power: 2200 VA for 2200 W of real power — its power factor of 1 makes all of the rated power available in watts. Outlets: 4 French-standard outlets — plug your devices in directly, no adapter needed. Management: USB port and RS-232 serial port for automatic shutdown; slot for an SNMP network card. Pure sine wave output; low-noise operation (under 40 dB). Ideal, for example, for a server, a demanding workstation or network equipment. Remember to check how much power your equipment draws and to choose the rating according to the runtime you need.
176 - 276 V without derating (up to 100 - 276 V with derating)
Battery replacement
User-replaceable, hot-swappable (no power interruption)
Battery management
ABM® or temperature-compensated charging method (user-selectable), automatic battery test, deep discharge protection, automatic recognition of external batteries
Interface port
1 USB port, 1 RS232 serial port, 1 remote ON/OFF mini terminal block, 1 remote power-off mini terminal block, 1 output relay mini terminal block
User interface
Multilingual graphic LCD display
Audible alarm
Yes
Power management software
Eaton Intelligent Power
Weight (kg)
24.5 kg
Dimensions (W x D x H) (mm)
440 x 485 x 130 mm
Technology
On-line
Power (VA)
2,200 VA
Voltage stabiliser
Yes
Box contents
Feet · Rack mounting kit
Technical specifications (continued)
Communication card slot
1 slot for Network-MS, ModBus-MS or Relay-MS card (optional)
Rack height
3U
Transfer/switching time
0 ms (continuous double conversion)
Bypass
Internal bypass + HotSwap MBP maintenance bypass as standard
Audible noise
< 40 dBA
Power factor (ratio)
1
Input power factor
Input power factor correction (PFC), ratio not published by the manufacturer
Output frequency
50 - 60 Hz
Phase (output/input)
Single-phase / Single-phase
Eco mode efficiency
98% in high-efficiency mode
Double-conversion efficiency
Up to 93% in online mode
Output type
FR outlets
Power (W)
2,200 W
Runtime
43 min at 300 W; 25 min at 500 W; 15 min at 800 W; 9 min at 1,200 W; 5 min at 1,800 W
External battery packs
Up to 4 hot-swappable external battery modules (EBM 9PXEBM72RT3U)
Form factor
Convertible rack/tower
Battery-backed outlets
3 to 4 outlets
Control & communication
USB, RS232 serial port, Card slot
Warranty
1 year
Specific references
EAN
743172081452
Customer reviews
No reviews yet
Be the first to review this product and help other customers.
Write a review
Frequently asked questions about this product
Does this 9PX 2200 have French outlets?
Yes, and that is what sets it apart: four French outlets on the output side, into which you plug your devices directly — with no adapter or IEC cord, unlike almost every other UPS in this range.
Does this 2200 VA unit really deliver 2200 W?
Yes: the power factor is 1, so the full 2200 VA is available in watts. On a conventional UPS with French outlets, whose power factor is around 0.6, only 1320 would be left.
How does the 9PX2200IRTBPF connect to the mains?
Via a heavy-duty C20 inlet — the 16 A format, not the C14 of a desktop UPS. The input voltage can be set to 200, 208, 220, 230 or 240 V, within an accepted range of 176 to 276 V.
What is the benefit of this model's shallow 3U format?
It is only 485 mm deep, for 440 wide and 130 high, i.e. 3U. It therefore fits into shallow cabinets where a longer 2U UPS will not, and converts to a tower.
Is the output a pure sine wave?
Yes, the output is a pure sine wave, continuously regenerated by double conversion with power factor correction. The output frequency is held at 50 or 60 Hz.
How do you monitor the 9PX2200IRTBPF?
Through a USB port, an RS-232 serial port and three mini terminal blocks — remote on/off, remote power off, relay output. A slot accepts a Network-MS, ModBus-MS or Relay-MS card.
Is this 9PX 2200 with French outlets noisy?
It stays below 40 dBA, which is low for a 2200 VA double-conversion unit. Allow for 24.5 kg: at this weight, the unit sits on the floor or is mounted at the bottom of the rack.
Is the Eaton 9PX 2200 RT3U (9PX2200IRTBPF) new and under warranty?
Yes, new equipment, with the invoice serving as the warranty document. It displays its status on a multilingual graphical LCD screen, and its battery can be extended with an external EBM 3U module.
Twenty minutes of runtime at half load (2 400 W), extended to several hours with up to four external battery cabinets. The standard maintenance bypass allows the unit to be swapped without shutting down the equipment.
•Around 20 minutes of runtime at half load (2 400 W)
•Runtime extendable with one to four external battery cabinets
•Internal bypass and maintenance bypass as standard
Every outlet is battery-backed, with around 11 minutes of runtime at half load (990 W). Automatic and manual internal bypass, LCD screen and a detachable 2.44 m cord supplied.
Floor-standing, 68.5 cm high and 54 kg: the tower version, for when there is no rack. Around 11 minutes of runtime at half load (3000 W) and 94% efficiency at full load.
Doubling the runtime comes down to one extra battery cabinet: 9 minutes at half load become 23 minutes. The 16 12 V batteries are chosen and ordered separately.
Up to four external battery modules extend the 10.5 minutes of runtime at half load. The 2U rack mounting kit, the output cords and the USB cable are included.
•Runtime: 10.5 min at half load, 3.5 min at full load
•Runtime extendable by up to 4 external battery modules
•C13 outlets: the format of computer and server power cords
Built-in network card: monitoring and control happen remotely, from the company network. 1980 W genuinely available and ten output sockets, two of them reinforced 16 A, in a chassis meant for the rack.
Four U in a rack and a battery recharged in 3 hours: it is ready to go again quickly after a cut. Around 11 minutes of runtime at half load (3000 W) and 7 minutes at 70%.
Nineteen minutes of runtime at half load, extended to fifty with an additional battery cabinet. The 16 12 V batteries are chosen and ordered separately.
A maintenance bypass supplied as standard allows the UPS to be replaced without shutting down the equipment it powers. Around 15 minutes of runtime at half load (4 000 W), extendable with four battery cabinets.
•Around 15 minutes of runtime at half load (4 000 W)
•Runtime extendable with one to four external battery cabinets
For a whole infrastructure: 9 minutes of runtime at half load (5000 W) and 5 minutes at 70%, the time it takes to switch over to a generator. 94% efficiency at full load and internal bypass.
•Runtime 9 minutes at 50% load (5000 W)
•
•Around 11 minutes of runtime at 50% load (990 W), 7 minutes at 70% (1 386 W)
•All output outlets are battery-backed
•C13 outlets in the format used by computer and server power cords, C19 outlets heavy-duty at 16 A
In stock
19 499 DHincl. VAT19 499,00 DHincl. VAT
Delivery everywhereDelivered all over Morocco
Runtime 7 minutes at 70% load (4200 W)
•Tower format, floor-standing
In stock
18 599 DHincl. VAT18 599,00 DHincl. VAT
Delivery everywhereDelivered all over Morocco
Runtime with the 16 internal batteries: 9 min at 50% load, 23 min at 25%
•With an additional battery cabinet: 23 min at 50% load, 60 min at 25%
•Batteries to be ordered separately: 16 12 V batteries of 7 or 9 Ah
In stock
16 299 DHincl. VAT16 299,00 DHincl. VAT
Delivery everywhereDelivered all over Morocco
In stock
14 799 DHincl. VAT14 799,00 DHincl. VAT
Delivery everywhereDelivered all over Morocco
•
Built-in network card to monitor and control the UPS remotely
•1980 W genuinely available
•8 C13 outlets, the format of computer and server power cords
In stock
27 099 DHincl. VAT27 099,00 DHincl. VAT
Delivery everywhereDelivered all over Morocco
•
Runtime 7 minutes at 70% load (4200 W)
•Height 4U in a rack
In stock
27 299 DHincl. VAT27 299,00 DHincl. VAT
Delivery everywhereDelivered all over Morocco
•Runtime with the 16 internal batteries: 19 min at 50% load, 50 min at 25%, 6 min at full load
•With an additional battery cabinet: 50 min at 50% load, 115 min at 25%
•Batteries to be ordered separately: 16 12 V batteries of 7 or 9 Ah
2400 W genuinely available and 13.5 minutes of battery life at half load (1200 W): time enough to save and shut down cleanly. Under 37 dB, it can stay beside the workstation it protects.
Every outlet is battery-backed, with around 11 minutes of runtime at half load (990 W). Automatic and manual internal bypass, LCD screen and a detachable 2.44 m cord supplied.
26 minutes of runtime for 400 W drawn, 12 minutes at half load (800 W): ample time to save and shut down cleanly. The LCD display shows the load and the remaining runtime without any software.
16 minutes of runtime at half load (800 W), and under 37 dB: it can sit next to a workstation without being heard. Its batteries are replaced without cutting the power.
•16 minutes of runtime at half load (800 W)
•7 minutes of runtime at full load
•6 C13 outlets, the format used by computer and server cords
Quiet at under 37 dB, it holds 11.5 minutes at half load (400 W): enough to save and shut down a NAS or a small server without losing anything. Its batteries are replaced without cutting the power.
•11.5 minutes of runtime at half load (400 W)
•5 minutes of runtime at full load
•4 C13 outlets, the format used by computer and server cords
Up to four external battery modules extend the 10.5 minutes of runtime at half load. The 2U rack mounting kit, the output cords and the USB cable are included.
•Runtime: 10.5 min at half load, 3.5 min at full load
•Runtime extendable by up to 4 external battery modules
Compatible with Synology NAS units over USB: the NAS shuts itself down cleanly when the battery runs low. Around 6 minutes of runtime at half load (400 W), for under 40 dB in operation.
Three reinforced 16 A outlets for power-hungry hardware, eight server outlets, and batteries that are changed without cutting the power. Under 40 dB at one metre, in a rack as in a tower.
•8 C13 outlets: the format of computer and server power cords
Twenty minutes of runtime at half load (2 400 W), extended to several hours with up to four external battery cabinets. The standard maintenance bypass allows the unit to be swapped without shutting down the equipment.
•Around 20 minutes of runtime at half load (2 400 W)
A maintenance bypass supplied as standard allows the UPS to be replaced without shutting down the equipment it powers. Around 15 minutes of runtime at half load (4 000 W), extendable with four battery cabinets.
•Around 15 minutes of runtime at half load (4 000 W)